This standard refers to permanently installed light fixtures on the exterior of the building or the site/grounds (e.g., walkway lighting, pole lighting, wall packs, and canopy lights) that illuminate exterior areas (e.g., entryways, parking lots, and exterior stairwells). There are no requirements in these standards for site lighting placement or existence. However, all permanent lighting fixtures must not have :
- Missing components
- Damaged components such as light bulbs, sockets, and ballasts, or
- Fixtures that are loose, damaged, and/or not secure.
Def# | Deficiency | Severity | Repair Due | HCV Rating |
---|---|---|---|---|
1 | A permanently installed light fixture is missing | Moderate | 30 Days | Fail |
1 | A permanently installed light fixture is damaged | Moderate | 30 Days | Fail |
1 | A permanently installed light fixture is inoperable | Moderate | 30 Days | Fail |
1 | A permanently installed light fixture is not secure/loose | Moderate | 30 Days | Fail |
Lighting – Exterior Standard V3.0 Updated 6/16/23